Intumescent movement joint products have been tested to BS476 Part 20, for up to 4 hours fire protection.

Fire Rating

Joint size
mm 

 Fire rating

Seal 

Product size 
T x W
mm

 15-30

 2 hours

 Dual

 32 x 25

 

 4 hours

 Dual

 32 x 50

 31-50

 4 hours

 Dual

 52 x 50

 51-75

 4 hours

 Dual

 78 x 50


 