| Ablative Coated Batt |
|
Standards and approvals |
 |
Fire Rating The FirePro Coated Batt has been tested to prEN 1366-3 and is capable of providing fire resistance periods of 4 hours integrity and 2 hours insulation. The table below indicates the expected performance for various generic service types and supporting constructions.
Service type | Fire resistance¹ | Suppporting construction | | Integrity | Insulation | | None (Blank seal) | 4 hrs | 2 hrs | Masonry walls and concrete floors | Up to 2 hrs | 2 hrs | Plasterboard walls | Individual cables | Up to 4 hrs | ≥1 hr | Masonry walls and concrete floors | | Up to 2 hrs | ≥1 hr | Plasterboard walls | Cables supported on trays or ladders | Up to 4 hrs | ≥1 hr | Masonry walls and concrete floors | | Up to 2 hrs | ≥1 hr | Plasterboard walls | | Steel and copper pipes (insulated) | Up to 4 hrs | ≥1 hr | Masonry walls and concrete floors | | Up to 2 hrs | ≥1 hr | Plasterboard walls | Steel and copper pipes (un-insulated) | Up to 4 hrs | n/a | Masonry walls and concrete floors | | Up to 2 hrs | n/a | Plasterboard walls | | Plastic pipes | Up to 4 hrs | ≥1 hr | Masonry walls and concrete floors | | Up to 2 hrs | ≥1 hr | Plasterboard walls |
¹Performance to be assessed to BS 476:Part 20 until EN standard is finalised
|
|
|
| Back
| |
|
| |
|
Rockwool Limited, Pencoed, Bridgend, CF35 6NY, UK
| 01656 862621 |
|
Copyright © Rockwool Limited, Disclaimer |
|
|
|