Rockwool Ltd > Rockwool Solutions > Products > Firepro > Intumescent Pipe Wraps > Intumescent Pipe Wrap installation


House Insulation
Technical Centre
Coated batt section
Environment
Rockwool UK


new service information section


Home

Careers

Contact

News



Add to My Favorites  MY FAVORITES







Printer friendly page
  Intumescent Pipe Wraps


Fire Stopping - Compartment Walls & Floors– Services and Cables  

The product is manufactured to be wrapped around the outside diameter of the pipework or trunking and is secured by means of a self-adhesive strip. The Intumescent Pipe Wrap is then positioned within the compartment wall or floor so that the edge of the product is left exposed at the face of the wall or soffit.
 
1) Check that pipe surface is clear of mortar.
  
2) Ensure that the correct pipe band is installed to suit diameter and fire rating.
 
3) Wrap around pipe and fix with integral self-adhesive strip.
 
4) Slide into position ensuring that the bottom edge is exposed in a floor slab and both edges are exposed in the wall. Two bands may be necessary when the wall thickness exceeds 150mm.
 
5) Seal the pipe band into the structure with Rockwool Firestop Compound.

Intumescent pipe wrap
Pipe Wrap positioned
level with underside
of floor slab

Intumescent pipe wraps
When using Rockwool
Corofil permanent
shuttering, leave
approximately 15mm
gap around pipe


Intumescent pipe wraps
Single Pipe Wrap
in position in wall

Intumescent pipe wraps
Two Pipe Wraps may
be necessary for walls
over 100mm thick.
Ensure that edges
are exposed



 

| Back |

| Top |
 

Rockwool Limited, Pencoed, Bridgend, CF35 6NY, UK
| 01656 862621 |     |
Copyright © Rockwool Limited, Disclaimer