| Acoustic Intumescent Sealant |
|
Standards and approvals |
 |
Acoustic Intumescent Sealant is a high specification, one part water based acrylic sealant, extruded from a cartridge loaded into a standard sealant gun. The depth of the joint will depend on the gap to be filled and the fire rating required. All surfaces must be thoroughly clean and free of bond breaking contaminants prior to application of the sealant. No priming is required for most construction substrates; however, it is recommended that a small area be tested on substrates. The sealant should not be applied if the ambient temperature is below 5°C as adhesion will be impaired. The sealant is fast curing, approximately 15 minute tack free time. When fully cured the sealant can be overpainted.
Joint Size mm | Depth of Sealant mm | Integrity mins | Insulation mins | Backing | Type of seal | | | | | | | | | | | | | | | | | | | 20 |
20 | 240 | 60 | Linear Firestop 2* | Single | | | | | | | 30 | 5 | 240 | 60 | Linear Firestop 2* | Single |
* See Linear and Trapezoidal Firestop Systems data sheet.
Acoustic Performance Weighted Sound Reduction Index (Rw) of up to 57db.
|
|
|