Rockwool Ltd > Rockwool Solutions > Products > Firepro > Acoustic Intumescent Sealant > Acoustic Intumescent Sealant


House Insulation
Technical Centre
Coated batt section
Environment
Rockwool UK


new service information section


Home

Careers

Contact

News



Add to My Favorites  MY FAVORITES






Acoustic Intumescent Sealant


Standards and approvals
FIRAS logo  Metronet  ASFP logo

Acoustic Intumescent Sealant is a high specification, one part water based acrylic sealant, extruded from a cartridge loaded into a standard sealant gun. The depth of the joint will depend on the gap to be filled and the fire rating required. 
 
All surfaces must be thoroughly clean and free of bond breaking contaminants prior to application of the sealant. No priming is required for most construction substrates; however, it is recommended that a small area be tested on substrates.
 
The sealant should not be applied if the ambient temperature is below 5°C as adhesion will be impaired.
 
The sealant is fast curing, approximately 15 minute tack free time.
 
When fully cured the sealant can be overpainted.
                                                    

Joint Size
mm

Depth of
Sealant
mm

Integrity
mins

Insulation
mins

Backing Type of seal 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

20

240

60

Linear Firestop 2*

 Single

 

 

 

 

 

30

5

240

60

Linear Firestop 2*

 Single


* See Linear and Trapezoidal Firestop Systems data sheet.

Acoustic Performance
Weighted Sound Reduction Index (Rw) of up to 57db.

 

| Back |

| Top |
 

Rockwool Limited, Pencoed, Bridgend, CF35 6NY, UK
| 01656 862621 |     |