| Fire Duct Systems |
Fire Protection - HVAC– Circular Ducts Circular steel ducts of between 60mm and 356mm diameter may be protected using Fire Duct Section.
Fire Duct Section must be glued with FirePro Glue at the joints and in the grooves. Steel bands or wires must be fitted circumferentially to the system at 300mm nominal centres to hold all joints and grooves tightly closed while the glue cures.
Where required, cover strips and bearer protection pieces are to be cut from Fire Duct Section (or Fire Duct PSM) of the appropriate diameter.
The foil covering is to be removed from the area of Fire Duct Section immediately beneath the cover strips prior to gluing into position and securing with steel nails or pins.
Self adhesive aluminium foil tape may be used to seal the joints where a vapour barrier is required.
The hanger system is as described on page 40, with the angle bearer formed into a circular shape to suit the diameter of the duct or the Fire Duct Section (depending on whether the hanger is located inside or outside the protection).
Fire Duct Section is used to protect the drop rods as described on page 40. General installation principles are as otherwise described in this manual for Fire Duct Slab.
|
Fire Duct PSM
Circular steel ducts of 406mm and greater diameter may also be protected using Fire Duct PSM.
Fire Duct PSM must be glued at the joints and in the grooves with FirePro Glue. Steel bands or wires must be fitted circumferentially to the system at 300mm nominal centres to hold all joints and grooves tightly closed while the glue cures.
General duct, hanger and installation details are as described for Fire Duct Section.
Notes to Figures 1 Circular steel duct to DW/144 2 Fire Duct Section/Fire Duct PSM 3 M10 steel drop rods at 1500mm maximum centres 4 Fire Duct Slab/Section – protection to hanger system 5 30 × 30 × 3mm minimum steel angle bearer |
 Fire Duct Section applied to circular duct
 Fire Duct PSM applied to circular duct
|
|
|