| U Values - Scotland, Scottish Building Standards |
The guidance gives three alternative approaches to the design of the insulation envelope of dwellings. These are:
. Elemental method . Heat loss method . Carbon Emissions calculation method |
Domestic To use the Elemental method, individual exposed building elements and other elements forming the insulation envelope of a dwelling or a building consisting of dwellings should have a U value which do not exceed the value given in the table below.
There are two levels of U value; Column A and column B. Column selection depends on the type of heating system to be installed in a dwelling and whether or not it has a central heating boiler with a SEDBUK of at least the percentages given in the table below.
Maximum U values for building elements using the Elemental method
Exposed element | With boiler min. SEDBUK % ( see table below) W/m2K | Other heating system W/m2K | Pitched Roof ins. between rafters ins. between joists | 0.20 0.16 | 0.18 0.16 | | Flat roof or roof (including pitched) with integral insulation | 0.25 | 0.22 | | Exposed wall, external wall | 0.30 | 0.27 | | Exposed floor or floor | 0.25 | 0.22 | Windows, doors and rooflights metal frames (area weighted average) wood on PVC frames (area weighted average) | 2.20 2.00 | 2.00 1.80 |
 Domestic - with boiler SEDBUK Minimum boiler SEDBUK which allows U values in Column A of the above table to be used| Central heating system fuel and boiler type | Minimum SEDBUK (%) | | Mains natural gas (all boiler types) | 78 | | LPG (all boiler types) | 80 | | Oil (combination boilers) | 82 | | Oil (all other types of boilers) | 85 |
 Domestic - more demanding, other heating systems
|
|
|
Non domestic To use the Elemental method, individual exposed building elements and other elements forming the insulation envelope of a dwelling or a building consisting of dwellings should have a U value which do not exceed the value given in the table below.
Maximum U values for building elements usind the Elemental Method Exposed element | W/m2K
| Pitched roof ins. between rafters ins. between joists | 0.20 0.16 | | Flat roof or roof (including pitched) with integral insulation | 0.25 | | Exposed wall, external wall or wall | 0.30 | | Exposed floor or floor | 0.25 | Windows, doors and rooflights metal frames (area weighted average) wood on PVC frames (area weighted average) | 2.20 2.00 | | Vehicle access and similar large doors (including doors located in walls) | 0.70 |
|
 Non domestic |
|
|
|