House Insulation
Technical Centre
Coated batt section
Environment
Rockwool UK


new service information section


Home

Careers

Contact

News



Add to My Favorites  MY FAVORITES




      home

The FirePro Coated Batt has been tested to prEN 1366-3 and is capable of providing fire resistance periods of 4 hours integrity and 2 hours insulation. The table below indicates the expected performance for various generic service types and supporting constructions.





Ask a question

Ask us a question about our coated batt or product range


 Service type

 Fire resistance ¹

 Supporting construction

 None (Blank seal) 

 4 hrs

  2 hrs 

 Masonry walls and concrete floors
 up to 2 hrs

 2 hrs

 Plasterboard walls

 Individual cables up to 4 hrs

 ≥ 1 hr

 Masonry walls and concrete floors
 up to 2 hrs

 ≥ 1 hr

 Plasterboard walls

 Cables supported on
 trays or ladders
             
 up to 4 hrs

 ≥ 1 hr

 Masonry walls and concrete floors
 up to 2 hrs

 ≥ 1 hr

 Plasterboard walls





Download Now


Download our FirePro product guide


 Steel and copper pipes  
 (insulated)
 up to 4 hrs ≥ 1 hr  Masonry walls and concrete floors
 up to 2 hrs ≥ 1 hr

 Plasterboard walls

 Steel and copper pipes
 (un-insulated)
 up to 4 hrs 

 n/a

 Masonry walls and concrete floors
 up to 2 hrs

 n/a

 Plasterboard walls

 Plastic Pipes up to 4 hrs

≥ 1 hr

 Masonry walls and concrete floors
 up to 2 hrs

≥ 1 hr

 Plasterboard walls






Contractor Rebate Offer

Click to register now.
¹ Performance to be assessed to BS 476:Part 20 until EN standard is finalised

 

 

| Back |

| Top |
 

Rockwool Limited, Pencoed, Bridgend, CF35 6NY, UK
|  01656 862621 |  | Sitemap
Copyright © Rockwool Limited, Disclaimer